Basic Motor Protection – C

Contact Seller

Transfer, Cash

Out of stock/ indent 2 s/d 4 week

Spain

  • Gives excellent protection for L.V. motors up to 1000 Vac
  • Broad range of current adjustment (1 to 630 and over)
  • Discriminative signalling of the relay trip cause
  • Suitable for any type of motor start or working cycle. Three types of adjustement for trip class, 10, 20 and 30
  • Memorizes the thermal image of the motor, either heating or cooling
  • External display module (22,5 mm)
  • Three-year guarantee
 

Model

Code

Range Motor 400 V Protections - Functions
Aux. supply 230V Aux. supply 115V  (A)

HP

kW

 Sobrecarga-Overload  Falta_Fase-Phase_Loss_Imbalance

C9

11203

11202

3 – 9,3 2 – 5,5 1,5 – 4

✓

✓ 

C21

11223

11222

9 – 21,6 7,5 – 12 5,5 – 9

✓ 

✓ 

C45

11243

11242

20 – 45,2 15 – 30 11 – 22

✓

✓ 

Applications

This relay is especially applicable to protect motors which need dependable and accurate protection relays for every type of start (trip classes 10, 20 and 30):

  •     Motor Control Centre (MCC)
  •     Pumps
  •     Compressors
  •     Ventilators
  •     Centrifugal Machines
  •     Conveyor Belts
  •     Cranes
  •     Valves
  •     Air conditioning
  •     Machine Tools
  •     Etc.

Technical Parameters

Termal memory / Overload Trip Yes/From  1,1 x IB
Maximum Motor Nominal Voltage 100 Vac
Trip Clases (IEC 947-4-1) 10-20-30
Phase Imbalance Protection Over 40% tripping time <3s
Reset Mode Manual and Remote
Signalling LED’s 3 LED’s
Output Contacts 1 relay with 1 NO + 1 NC
Switching Power Ith: 5A; AC15 – 250V -2A; DC13 – 30V – 2A
Terminals: Max. section / screw torque 2,5 mm2, No. 22 – 12AWG  / 20Ncm, 1,8 LB – IN
Power Consumption C9: 6,5VA (230 Vac); 3VA (115Vac)/C21 – C45: 2,5VA
Protection degree / weight / mounting IP20 / 0,3 kg / DIN rail
Storage Temperature -30º / +70º
Operation Temperature / Max. Altitude -15º +60ºC / 1.000m ; -15º +50ºC / 3.000m
Standards IEC 255, IEC 947, IEC 801, EN 50081-2
  CE UL-US LISTED

Trip Curves

Cold curve: represents the performance of the relay without any previous current flow, first start. Warm curve: the tripping times decrease as the current flows, and are adapted to the motor heating condition based on the thermal memory, the warm condition (IEC-255) is reached after a current of 0.9 x IN (motor rated current) flows during 2 hours approximately.

Connections

 

External Display

  • Optional display module
  • Size of 22mm push button
  • Mounted externally, on the panel door or a draw-out unit in a motor control centre (CCM)
  • Connected to the relay by a flat cable L= 2 meters
  • Diagramas conexiones cThe module has the appropriate LED’s to signal the trip cause and a reset push-button.

 

Dimensions